| Hubbell Wiring Device-Kellems Product
Specifications |
| Hospital Product Type |
|
| Hospital Grade Receptacle
Type |
Duplex |
| Duplex Receptacle Type |
Rectangular Face |
| Amperage |
15A |
| Voltage |
125V |
| Color |
|
| NEMA Number |
5-15R |
| Horsepower |
0.05 |
| Description |
Hospital Grade Straight Blade
Duplex Receptacle |
| Type |
2 Pole, 3 Wire, Grounding
|
| Certification |
UL Listed Fed Spec WC596F1,
Hospital Grade Meets NEMA WD-1 and WD-6 Requirements. Listed to UL
Standard 498, Certified to CSA, C22.2, No. 42 where applicable
|
| Top Material |
Nylon |
| Base Material |
Reinforced PET |
| Power Contacts Material |
.037" (.9) Phosphor Bronze
|
| Ground Contacts
Material |
.032" (0.8) Brass |
| Mounting Strap Material |
.050" (1.3) Steel Galvanized
|
| Terminal Screw Material |
#8-32 Brass /Ni plated for
neutral |
| Ground Screw Material |
#8-32 Brass, Multiple Drive
(Green) |
| Auto. Ground. Clip
Material |
Stainless steel |
| Mounting Screws
Material |
Steel-Zinc Plated |
| Dielectric Voltage |
Withstands 2,000V minimum.
|
| Current Interrupting |
Certified for current
interrupting at full rated current. |
| Temperature Rise |
Max 30°C temperature rise at
full rated current after 50 cycles of overload at 150% of rated
current with direct current. |
| Terminal Identification |
Terminals identified in
accordance with UL498 (Brass, White, Green). |
| Terminal Accommodation |
#14-#10 AWG copper conductor
only. |
| Product Identification |
Ratings are a permanent part of
the device. |
| Flammability |
UL 94 V0 and UL 94-5 VA. |
| Operating Temperatures |
Maximum continuous 75°C,
minimum -40°C (w/o impact). |